Technical Data

Product Selection Guide


QM1L Thermo-magnetic type MCCB with Earth-Leakage protection

QM1L160SP4
Product codeFrame sizeCurrent classCode of control circuit source voltagePole number
Residual-current circuit breaker125, 160, 250, 630, 800
Note:
125 is upgraded type of 63 frame
160 is upgraded type of 100 frame
225 is upgraded type of 250 frame

SMHP: electric operation
Z: rotary handle
W: direct operation
3: 3-pole
4: 4-pole
12525/18-1.435/25
16025/18
50/35
25025/1835/2550/35
40035/25-65/65
800--65/65


300160A2A
Release type and internal accessoryRated current (A)ApplicationCode of four-pole product
The first digit represents
release type
2 :has  instantaneous
release only  
3 :complex release
Note:Later two digits are
the code of accessories
(see accessory table)
125:10, 16, 20, 25, 32, 40, 50, 63, 80, 100, 125
160:63, 80, 100, 125, 140, 160
250:100, 125, 140, 160, 180, 200, 225, 250
400:250, 300, 315, 350, 400
800:500, 630, 700, 800
1: power distribution
2: motor protection
A: N-pole without protection
cannot close or open
B: N-pole without protection
can close and open
C :N-pole with protection
can close and open
D: N-pole with protection
cannot close or open
Note:Unless otherwise mentioned,
4-pole products will be classified
as CAT. B by default.


L1Y1 
Rated residual operating current (mA)Rated delay time (if selected) 
Delay fixed typeQuick three-gear adjustableDelay fixityDelay three-gear adjustable
L1: 30
L2: 50
L3: 75
L4: 100
L5: 150
L7: 200
L8: 300
L9: 500
L10: 1000
L11: 30, 50, 100
L12: 30, 100, 200
L13: 30, 100, 500
L14: 100, 200, 300
L15: 100, 300, 500
L16: 300, 500, 1000
Y1: 0.1s Y4: 0.4s Y7: 0.7s Y10: 1.0s
Y2: 0.2s Y5: 0.5s Y8: 0.8s Y11: 1.5s
Y3: 0.3s Y6: 0.6s Y9: 0.9s Y12: 2.0s
Y13: 0.45、1、2
Y14: 1、2、3(s)


Q1D1Q2
Accessory voltageElectric operation voltageInstallation methodsInstall wiring
Undervoltage releaseShunt releaseAuxiliary alarmDC1 ElectricDC3 ElectricQ: Front-board
H: Back-board
C: Plug-in type
1: No
2: Yes



OperationOperation
Q1: AC220VF1: AC220VJ1: AC125VD1: AC220VD5: AC230V
Q2: AC240VF2: AC380VJ2: AC250VD2: AC230VD6: AC110V
Q3: AC380VF3: DC110VJ3: DC125VD3: AC380VD7: DC220
Q4: AC415VF4: DC24VJ4: DC24VD4: AC400VD8: DC110

D9: AC110-240V

D10: DC100-220V

Note:
Adaptable voltages for two electric operations.
Please refer to the introduction of external accessory.


Main Performance Indexes

Frame current (A)125160
ModelQM1L-125SQM1L-125HQM1L-160SQM1L-160MQM1L-160H
Pole number2, 3, 42, 3, 43, 4

QM1L Thermo-magnetic type MCCB with Earth-Leakage protectionQM1L Thermo-magnetic type MCCB with Earth-Leakage protection
Power supply system3P3Φ3W, 1Φ2W, 1Φ3W3Φ3W, 1Φ2W, 1Φ3W
4P3Φ4W3Φ4W
Rated current (A)10, 16, 20, 32, 25, 40, 50, 63, 80, 100, 12563, 80, 100, 125, 140, 160
Rated voltage (V)AC400V
Rated insulation voltage (V)AC690V
Short-circuit breaking capacity(KA)Icu/IcsAC400V25/1835/2525/1835/2550/35
Operating cycle numberElectrical life600060003000
Mechanical life900090007000
Quick typeRated residual operating current30, 100, 500(adjustable)
Max. actuation time0.1
Delay typeRated residual operating current100, 300, 500(adjustable)
Max. actuation time-
Max. actuation time under 21△n (s)0.45, 1.0, 2.0(adjustable)
Inertia non-actuation time under 21△n (s)0.1, 0.5, 1.0-
Outline dim(mm)

a-b-c-ca


QM1L Thermo-magnetic type MCCB with Earth-Leakage protection

2P50-130-68-9060-155-68-90
3P75-130-68-9090-155-68-9090-155-88-115
4P100-130-68-90120-155-68-90120-155-88-115
2P0.550.750.750.75
3P0.650.851.21.2
4P0.81.21.51.5
Electric operating device (MD)
External driving operating handle
Automatic releaseThermal electromagnetic type


Frame current (A)250
ModelQM1L-250SQM1L-250MQM1L-250H
Pole number3, 4

QM1L Thermo-magnetic type MCCB with Earth-Leakage protection
Power supply system3P3Φ3W, 1Φ2W, 1Φ3W

4P3Φ4W
Rated current (A)100, 125, 140, 160, 180, 200, 225, 250
Rated voltage (V)AC400V
Rated insulation voltage (V)AC690V
Leakage indication systemButton
Short-circuit breaking capacity(KA)Icu/IcsAC400V25/1835/2550/35
Operating cycle numberElectrical life3000
Mechanical life7000
Quick typeRated residual operating current30, 100, 500(adjustable)
Max. actuation time0.1
Delay typeRated residual operating current100, 300, 500(adjustable)
Max. actuation time-
Max. actuation time under 21△n (s)100, 300, 500(adjustable)
Inertia non-actuation time under 21△n (s)0.1, 0.5, 1.0
Outline dim(mm)

a-b-c-ca


QM1L Thermo-magnetic type MCCB with Earth-Leakage protection

2P-
3P105-165-68-92105-165-88-115
4P140-165-68-92140-165-88-115
 Weight (kg)2P--
3P22.1
4P2.52.6
Electric operating device (MD)
External driving operating handle
Automatic releaseThermal electromagnetic type


Frame current (A)400800
ModelQM1L-400SQM1L-400HQM1L-800H
Pole number3, 4

QM1L Thermo-magnetic type MCCB with Earth-Leakage protectionQM1L Thermo-magnetic type MCCB with Earth-Leakage protection
Power supply system3P3Φ3W, 1Φ2W, 1Φ3W
4P3Φ4W
Rated current (A)250, 315, 350, 400500, 630, 700, 800
Rated voltage (V)AC400V
Rated insulation voltage (V)AC690V
Leakage indication systemButton
Short-circuit breaking capacity(KA)Icu/IcsAC400V35/2565/6565/65
Operating cycle numberElectrical life2000
Mechanical life4000
Quick typeRated residual operating current30, 100, 500(adjustable)
Max. actuation time0.1
Delay typeRated residual operating current100, 300, 500(adjustable)
Max. actuation time-
Max. actuation time under 21△n (s)0.45, 1.0, 2.0(adjustable)
Inertia non-actuation time under 21△n (s)0.1, 0.5, 1.0
Outline dim(mm)

a-b-c-ca


QM1L Thermo-magnetic type MCCB with Earth-Leakage protection

2P-
3P140-257-103-155210-257-103-155
4P185-257-103-155280-257-103-155
Weight (kg)2P--
3P6.612.5
4P8.417.5
Electric operating device (MD)
External driving operating handle
Automatic releaseThermal electromagnetic type


QM1L Thermo-magnetic type MCCB with Earth-Leakage protection

QM1L Thermo-magnetic type MCCB with Earth-Leakage protection

QM1L Thermo-magnetic type MCCB with Earth-Leakage protection

QM1L Thermo-magnetic type MCCB with Earth-Leakage protection

QM1L Thermo-magnetic type MCCB with Earth-Leakage protection

QM1L Thermo-magnetic type MCCB with Earth-Leakage protection

QM1L Thermo-magnetic type MCCB with Earth-Leakage protection